{"id":"fire-alarm-panel","version":"0.5.0","classification":{"uniformat":"D5030"},"names":["Fire alarm control panel"],"aliases":["FACP","fire panel","fire alarm"],"service_life":{"median_years":20,"range_years":[15,25],"range_basis":"source_spread"},"pm_tasks":[{"task":"Inspect panel condition: connections, fuses and LEDs (unmonitored panels)","frequency":"P1M","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Resolve any trouble indications (unmonitored panels)","frequency":"P1M","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Test receipt of alarm, supervisory and trouble signals and operation of outputs","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Verify all lamps and LEDs are lit","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Load test backup batteries with a meter","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Check condition of power supplies and batteries","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Check manual pull stations are accessible","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":34,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Test notification appliances (horns, strobes, speakers) work","frequency":"P1Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":35,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Operate manual pull stations to check alarm is received","frequency":"P2Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":35,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"},{"task":"Test supervisory devices (low air, temperature, water level) signal the panel","frequency":"P2Y","reference":"UFC 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (7 October 2021, with Change 1, 18 April 2025)","url":"https://www.wbdg.org/FFC/DOD/UFC/ufc_3_601_02_2021_c1.pdf","page":35,"checklist":"Table 2-1 Fire Detection and Alarm System ITM Tasks"}],"basis":[{"type":"public_document","life_type":"planning","title":"CNA e-Tool Estimated Useful Life Table","by":"U.S. Department of Housing and Urban Development","url":"https://www.hud.gov/sites/documents/eul_for_cna_e_tool.pdf","page":15,"code":"HUD CNA 3.6.2.7","label":"Smoke and fire detection system, central panel","years":15,"note":"Same life for family and elderly properties. US multifamily housing."},{"type":"public_document","life_type":"accounting","title":"Meaford: By-law 2020-83, Tangible Capital Asset Policy, Appendix A Estimated Useful Lives","url":"https://meaford.civicweb.net/document/103944/","page":17,"years":25,"note":"Capital asset policy (amortization period). Approved on text check: the label and value were found on the cited page."},{"type":"public_document","life_type":"accounting","title":"The Blue Mountains: POL.COR.19.04 Tangible Capital Assets Policy","url":"https://www.thebluemountains.ca/sites/default/files/2022-01/POL-COR-19-04-Tangible-Capital-Assets-Policy.pdf","page":11,"years":20,"note":"Capital asset policy (amortization period). Approved on text check: the label and value were found on the cited page."},{"type":"public_document","life_type":"accounting","title":"Grey Highlands: By-law No. 2026-052, Tangible Capital Asset Policy A09-F-03","url":"https://greyhighlands.civicweb.net/document/406218/","page":11,"years":20,"note":"Capital asset policy (amortization period). Approved on text check: the label and value were found on the cited page."}],"confidence":{"grade":"C","sample_size":null},"open_questions":["HUD gives planning lives for US multifamily housing; the municipal rows are Ontario accounting lives. Neither is observed replacement data."],"contributors":["unfinished.one editors"],"last_reviewed":"2026-10-22","canonical_url":"https://unfinished.one/c/fire-alarm-panel","versioned_url":"https://unfinished.one/c/fire-alarm-panel/v/0.5.0","licence":"CC-BY-4.0","citation":"unfinished.one (2026). Fire alarm control panel, v0.5.0. https://unfinished.one/c/fire-alarm-panel/v/0.5.0"}