Uniformat D3060
Gas detector
A gas detector lasts about 10 years, as stated by the one published source on file.
Also listed as Gas detection system, CO detector, NO2 detection, refrigerant leak detector
Service life
Years in service. One stated life so far; the band will widen as sources are added.
Work out when yours is due for replacement
One source. This value rests on a single document (UFM 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (Unified Facilities Manual, 13 March 2026), p32). Treat it as that source's figure, not a settled life, until others confirm it.
Basis
- 10 years · UFM 3-601-02 Fire Protection Systems Inspection, Testing, and Maintenance (Unified Facilities Manual, 13 March 2026), p32 · Table 2-1 “Fire Detection and Alarm System ITM Tasks, frequency "10 Years": "Carbon Monoxide Detectors" - "Replace detectors."” — U.S. Department of Defense (Unified Facilities Criteria program) (planning life)Printed page 25. CO detectors connected to the building fire alarm system (section 3-4 distinguishes these from single-station CO alarms). Covers the CO detector heads only; NO2, refrigerant and combustible-gas detectors and the gas detection controller are not addressed.
How sources are chosen and recorded: sourcing policy.
Municipal lives for HVAC (D30)
48 municipalities in Ontario, British Columbia and Alberta state a life for HVAC as a whole, in 39 distinct tables: 10–50 years, median 20. 65 rows come from capital asset policies (accounting lives, used for amortization) and 6 from asset management plans (planning lives, used to forecast replacement). They describe the system rather than this component, and none is a measured life.
Years. Each dot is one stated life and each bar a stated range; equal values stack. Hollow marks are planning lives from asset management plans; filled marks are accounting lives from policies. The dashed line is the median. Policies that copy the same table count once.
All 61 stated lives
| Municipality | Covers | Years | Kind | Source |
|---|---|---|---|---|
| Trent Lakes | HVAC | 10 | accounting | p10 · 2009 |
| Fort St. James, Revelstoke, Rossland, Sicamous, Tumbler Ridge · same table | HVAC | 10–12 | accounting | p5, p9, p7, p9, p5 · 2010 |
| Okanagan-Similkameen | HVAC | 10–12 | accounting | p11 · 2023 |
| Salmo | HVAC | 10–12 | accounting | p6 · 2016 |
| Duncan, North Cowichan · same table | HVAC | 15 | accounting | p17, p9 · 2011 |
| Lantzville | HVAC | 15 | accounting | p11 · 2019 |
| Grey Highlands | Furnace, gas-fired | 15 | accounting | p11 · 2026 |
| Kapuskasing | HVAC | 15 | accounting | p14 · 2009 |
| Sarnia | HVAC | 15 | accounting | p1 |
| The Blue Mountains | Furnace, gas-fired | 15 | accounting | p11 · 2019 |
| Westlock | HVAC | 15–20 | accounting | p11 · 2021 |
| Meaford | Furnace, gas-fired | 15–25 | accounting | p17 · 2020 |
| Lloydminster | HVAC | 20 | accounting | p11 · 2023 |
| Lloydminster | HVAC | 20 | accounting | p11 · 2023 |
| Lloydminster | HVAC | 20 | accounting | p11 · 2023 |
| Lloydminster | HVAC | 20 | accounting | p11 · 2023 |
| Comox Valley | Plumbing, HVAC, Electrical | 20 | accounting | p6 · 2010 |
| Cranbrook | Plumbing, HVAC, Electrical | 20 | accounting | p9 · 2010 |
| Parksville | HVAC | 20 | accounting | p9 · 2023 |
| Telkwa | HVAC | 20 | accounting | p8 |
| Amherstburg | HVAC, Electrical | 20 | accounting | p8 · 2026 |
| Amherstburg | Ice plant compressor; Ice plant brine chiller; Arena dehumidifier | 20 | accounting | p8 · 2026 |
| Chapple | HVAC | 20 | accounting | p1 |
| Greater Napanee | Unit heater, gas-fired; Unit heater, hydronic | 20 | accounting | p16 · 2012 |
| Grey Highlands | HVAC | 20 | accounting | p11 · 2026 |
| Huron | HVAC | 20 | planning | p42 · 2025 |
| Huron | HVAC | 20 | planning | p57 · 2025 |
| Huron | HVAC | 20 | planning | p68 · 2025 |
| Huron | HVAC | 20 | planning | p77 · 2025 |
| Kenora | HVAC | 20 | accounting | p15 · 2026 |
| London | Plumbing, HVAC, Electrical | 20 | accounting | p2 · 2023 |
| Meaford | HVAC | 20 | accounting | p17 · 2020 |
| Prince Edward | HVAC | 20 | accounting | p34 · 2022 |
| Rainy River | HVAC | 20 | accounting | p11 · 2010 |
| Rainy River | HVAC | 20 | planning | p17 · 2026 |
| Severn | HVAC | 20 | accounting | p400 · 2019 |
| The Blue Mountains | HVAC | 20 | accounting | p11 · 2019 |
| Welland | HVAC, Electrical | 20 | accounting | p8 · 2021 |
| Bancroft, Centre Hastings, Hastings Highlands, Wollaston · same table | HVAC | 20–25 | accounting | p5, p4, p6, p5 |
| Orillia | HVAC | 20–25 | accounting | p19 |
| Vulcan County | HVAC, Electrical | 20–30 | accounting | p5 · 2024 |
| Canmore | HVAC | 25 | accounting | p10 · 2025 |
| Leduc | HVAC | 25 | accounting | p13 · 2019 |
| Duncan, North Cowichan · same table | HVAC, Electrical | 25 | accounting | p17, p9 · 2011 |
| Lantzville | Plumbing, HVAC, Electrical | 25 | accounting | p11 · 2019 |
| Tofino | HVAC, Electrical | 25 | accounting | p12 · 2009 |
| Amherstburg | Evaporative condenser | 25 | accounting | p8 · 2026 |
| Greater Madawaska, Quinte West · same table | HVAC | 25 | accounting | p17, p38 · 2025 |
| Greater Napanee | HVAC, Electrical | 25 | accounting | p16 · 2012 |
| Grey Highlands | HVAC | 25 | accounting | p11 · 2026 |
| Kingston | HVAC | 25 | accounting | p15 · 2016 |
| Kirkland Lake | HVAC, Electrical | 25 | accounting | p10 · 2020 |
| Orillia | Ice plant compressor; Evaporative condenser | 25 | accounting | p19 |
| Severn | HVAC | 25 | accounting | p400 · 2019 |
| Severn | HVAC | 25 | accounting | p400 · 2019 |
| The Blue Mountains | HVAC | 25 | accounting | p11 · 2019 |
| Brantford | HVAC | 30 | planning | p10 · 2025 |
| Greater Napanee | Ice plant brine chiller | 30 | accounting | p16 · 2012 |
| Simcoe | HVAC | 30 | accounting | p19 · 2025 |
| Brockton | HVAC, Electrical | 40 | accounting | p2 · 2009 |
| Meaford | HVAC | 50 | accounting | p17 · 2020 |
Of 71 rows, 4 were compared with an image of their page; 67 were matched to their page automatically (the label and number appear in the page text). Follow the page link before relying on an automatically matched row. About the policies · All approved rows as JSON
Preventive maintenance
2 tasks in 1 work order.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12Annual
Months from the schedule start. Download the tasks as CSV for a CMMS, or ask the MCP tool get_pm_schedule for dated visits.
Annual · 2 tasks
Source: Public Buildings Service Preventive Maintenance Guide (Public Buildings Maintenance Standards), CTRL-DDC-07-01Y Sensors - Electronic
Frequencies are ISO 8601 durations in the data (P3M = every 3 months).
Open questions
- Every source here is a published planning, design or accounting life. None is observed replacement data.
- Written for GSA contracted O&M in US federal buildings; job plans are generic and defer to manufacturer instructions, and the fire extinguisher plans only point to NFPA 10.
Know the answer? Send it with a source to [email protected].
Cite this
Citation
unfinished.one (2026). Gas detection system, v0.6.0. https://unfinished.one/c/gas-detection/v/0.6.0BibTeX
@misc{unfinished_gas_detection_0_6_0,
title = {Gas detection system},
author = {{unfinished.one}},
year = {2026},
version = {0.6.0},
url = {https://unfinished.one/c/gas-detection/v/0.6.0},
note = {CC BY 4.0}
}Licence CC BY 4.0 · How to cite · JSON · Versions: 0.6.0, 0.5.0, 0.2.0, 0.1.0