unfinished.one

Uniformat D2030

Sewage ejector pump

Also called ejector pump, lift station

  • Confidence C
  • Version 0.4.0 (permanent link)
  • Reviewed 2026-10-22

Service life

50 yearsas stated by one source
0510152025303540455055605050

Years in service. One stated life so far; the band will widen as sources are added.

One source. This value rests on a single document (CNA e-Tool Estimated Useful Life Table, p9). Treat it as that source's figure, not a settled life, until others confirm it.

Basis

  • 50 years · CNA e-Tool Estimated Useful Life Table, p9 · HUD CNA 3.4.1.1.7 “Sewage Ejectors” — U.S. Department of Housing and Urban Development (planning life)
    Same life for family and elderly properties. US multifamily housing.

How sources are chosen and recorded: sourcing policy.

Municipal lives for plumbing (D20)

26 municipalities in Ontario and British Columbia state a life for plumbing as a whole, in 18 distinct tables: 15–50 years, median 25. 34 rows come from capital asset policies (accounting lives, used for amortization) and 1 from asset management plans (planning lives, used to forecast replacement). They describe the system rather than this component, and none is a measured life.

Median 25 yearsKingston: Building Fixtures, 15 yearsMeaford: Plumbing - Water Treatment System, 15 yearsTrent Lakes: Mechanical Systems - Fixtures, 15 yearsComox Valley: HVAC systems, mechanical, plumbing, wiring, etc., 20 yearsCranbrook: HVAC, plumbing, lighting, etc, 20 yearsTelkwa: Electrical/Plumbing/Fire, 20 yearsLondon: Building Components - Services (HVAC, lighting, communication, plumbing etc.), 20 yearsMeaford: Plumbing - Fixtures, 20 yearsMeaford: Plumbing - Boiler, 20 yearsLantzville: Electrical, Mechanical, Plumbing, 25 yearsMeaford: Plumbing - Septic System, 25 yearsRainy River: Building Improvements - Electrical/Plumbing, 25 yearsRainy River: Building Improvements - Electrical/Plumbing, 25 yearsThe Blue Mountains: Septic System, 25 yearsGreater Napanee: E30 Chillers, Rink Piping, Fuel Storage Tanks, 30 yearsGrey Highlands: Septic System, 30 yearsThe Blue Mountains: Plumbing System, 30 yearsTrent Lakes: Mechanical Systems - Piping, 30 yearsParksville: Plumbing Infrastructure, 50 yearsGreater Madawaska and Quinte West: Piping, 50 yearsMeaford: Plumbing - System, 50 yearsMeaford: Plumbing - Cistern, 50 yearsThe Blue Mountains: Cistern, 50 yearsFort St. James, Revelstoke and 3 more: Electrical/Plumbing/Fire, 15–20 yearsOkanagan-Similkameen: Electrical/Plumbing/Fire, 15–20 yearsSalmo: Electrical/Plumbing/Fire, 15–20 yearsBancroft, Centre Hastings and 2 more: Electrical/Plumbing, 25–30 years0102030405060

Years. Each dot is one stated life and each bar a stated range; equal values stack. Hollow marks are planning lives from asset management plans; filled marks are accounting lives from policies. The dashed line is the median. Policies that copy the same table count once.

All 27 stated lives
MunicipalityAs writtenYearsKindSource
KingstonBuilding Fixtures15accountingp15 · 2016
MeafordPlumbing - Water Treatment System15accountingp17 · 2020
Trent LakesMechanical Systems - Fixtures15accountingp10 · 2009
Fort St. James, Revelstoke, Rossland, Sicamous, Tumbler Ridge · same tableElectrical/Plumbing/Fire15–20accountingp5, p9, p7, p9, p5 · 2010
Okanagan-SimilkameenElectrical/Plumbing/Fire15–20accountingp11 · 2023
SalmoElectrical/Plumbing/Fire15–20accountingp6 · 2016
Comox ValleyHVAC systems, mechanical, plumbing, wiring, etc.20accountingp6 · 2010
CranbrookHVAC, plumbing, lighting, etc20accountingp9 · 2010
TelkwaElectrical/Plumbing/Fire20accountingp8
LondonBuilding Components - Services (HVAC, lighting, communication, plumbing etc.)20accountingp2 · 2023
MeafordPlumbing - Fixtures20accountingp16 · 2020
MeafordPlumbing - Boiler20accountingp17 · 2020
LantzvilleElectrical, Mechanical, Plumbing25accountingp11 · 2019
MeafordPlumbing - Septic System25accountingp17 · 2020
Rainy RiverBuilding Improvements - Electrical/Plumbing25accountingp11 · 2010
Rainy RiverBuilding Improvements - Electrical/Plumbing25planningp17 · 2026
The Blue MountainsSeptic System25accountingp11 · 2019
Bancroft, Centre Hastings, Hastings Highlands, Wollaston · same tableElectrical/Plumbing25–30accountingp5, p4, p6, p5
Greater NapaneeE30 Chillers, Rink Piping, Fuel Storage Tanks30accountingp16 · 2012
Grey HighlandsSeptic System30accountingp11 · 2026
The Blue MountainsPlumbing System30accountingp11 · 2019
Trent LakesMechanical Systems - Piping30accountingp10 · 2009
ParksvillePlumbing Infrastructure50accountingp9 · 2023
Greater Madawaska, Quinte West · same tablePiping50accountingp17, p38 · 2025
MeafordPlumbing - System50accountingp16 · 2020
MeafordPlumbing - Cistern50accountingp16 · 2020
The Blue MountainsCistern50accountingp11 · 2019

Of 35 rows, 2 were compared with an image of their page; 33 were matched to their page automatically (the label and number appear in the page text). Follow the page link before relying on an automatically matched row. About the policies · All approved rows as JSON

Preventive maintenance

9 tasks in 3 work orders. Intervals that fall due together are one visit: the annual visit also covers the quarterly and semi-annual tasks.

  1. 1
  2. 2
  3. 3Qtr
  4. 4
  5. 5
  6. 6Semi
  7. 7
  8. 8
  9. 9Qtr
  10. 10
  11. 11
  12. 12Annual

Months from the schedule start. Download the tasks as CSV for a CMMS, or ask the MCP tool get_pm_schedule for dated visits.

Quarterly · 3 tasks

Source: TM 5-692-1 Maintenance of Mechanical and Electrical Equipment at Command, Control, Communications, Computer, Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities: Recommended Maintenance Practices, Table 18-3 Sewage lift station and sewage sump unit

TaskPage
Remove sediment and sludge from wet pit or sumpp144
Clean float switches and check pump sequencep144
Check control panel for moisture or corrosionp144

Semi-annual · 2 tasks

Source: TM 5-692-1 Maintenance of Mechanical and Electrical Equipment at Command, Control, Communications, Computer, Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities: Recommended Maintenance Practices, Table 18-3 Sewage lift station and sewage sump unit

TaskPage
Hose down pumps to remove sludgep143
Check running amps against nameplate and overload settingsp144

Annual · 4 tasks

Source: TM 5-692-1 Maintenance of Mechanical and Electrical Equipment at Command, Control, Communications, Computer, Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities: Recommended Maintenance Practices, Table 18-3 Sewage lift station and sewage sump unit

TaskPage
Pull pumps; check seal oil, seals, bearings, cable, impeller and volutep143
Megohm test between pump body and power leadsp143
Reinstall pumps and check rotation directionp143
Check check valves workp144

Frequencies are ISO 8601 durations in the data (P3M = every 3 months).

Open questions

  • HUD's 50 years for sewage ejectors may describe the basin and piping rather than the pump. Pump lives need a second source.
  • Only one source so far: HUD planning lives for US multifamily housing. Canadian and observed sources are needed.
  • Some maintenance intervals come from TM 5-692-1, an Army manual for mission-critical (C4ISR) facilities; they may be tighter than typical commercial practice.

Know the answer? Send it with a source to [email protected].

Cite this

Citation

unfinished.one (2026). Sewage ejector pump, v0.4.0. https://unfinished.one/c/sewage-ejector/v/0.4.0